68, Manifolds to t# 12345678
The X76CTM allows for the combining of two or
more tanks to generate the combined product vol-
ume of physically manifolded tanks. If tank 2 is
manifolded to tank 1, the reports for tank 1 will
contain the manifolded volumes, while those for
tank 2 will not.The same applies to the leak test.
The leak test for tank 1 will use the combined
product volume, while tank 2 will be independent.
Manifolding tanks is performed with Function 68.
The display has 8 characters for every tank where
the current tank is marked with a black block.
Manifolds to t# 12345678
1-8 to set/clr: ...* ...
Press the key, corresponding to the tank number to
be manifolded, to toggle the status of the tank (i.e.,
if tank is not manifolded, it will manifold and vice
versa). Pressing the digit that corresponds to the
current tank does not cause a change.To end
manifolding, press [DISPLAY].
..
76, High-Water Level Alarm
The high water alarm is set using Function 76.
High water level alarm
3.5 in
The high water alarm warns when the water level
has exceeded a preset level.When this set point is
exceeded, an audible/visual alarm is generated fol-
lowed by a printout of the alarm. The high water
alarm can be programmed to an external output
relay (Function 81). Information on the last water
alarm warning for each tank is stored in memory.
..
79,Theft Detect Threshold
Use Function 79 to set up the theft detect thresh-
old. A message will be displayed:
Theft detect threshold
10.0 gl
Enter the number of gallons loss that will make the
theft gallon alarm active and press [ENT.].
NOTE: This function is only active when in THEFT
DETECT MODE (Function 292).
..
82, Set Up Tank Alarm
The X76CTM can be configured to perform differ-
ent actions when an alarm occurs. For each event,
a relay can be assigned.The events supported
are:
be conducted.The higher it is, the easier it is to
enter a leak test, but the data could be noisier and
the results incorrect
.
Leak scatter
0.2 gl
The activity threshold is used to distinguish tank
leakage from real activity - delivery of sale. It can
be increased to the minimal throughput of the dis-
penser pump. By default this is 9 gl/h.
Activity threshold
9.0 gl
Temperature scatter controls what temperature
slope is acceptable to start a test.
Temp scatter
0.2 deg/h
Minimum test duration sets the minimum accept-
able test time to be used by the CSLD database.
Min test duration
15 min
A maximum test duration of 120 minutes is suffi-
cient for tanks up to 20,000 gallons. Increasing this
duration usually will not improve the result and
degrade the response time.
Max test duration
120 min
Precise wait after delivery can be entered to in-
crease the test precision, although it is not needed
in most cases.
Precise wait after delivery
360 min
This parameter allows the X76CTM to use a lower
threshold for the Precise Test. Generally, this
increases the probability of false alarms, but allows
for early warning of possible tank leak.
0.1 gph test? No
The minimum CSLD duration sets a minimum com-
bined test time for the CSLD algorithm to make its
conclusions. Generally, the longer it is, the better.
Min CSLD duration
8 hours
The minimum history parameter sets the maximum
number of days to be used by CSLD to acquire the
minimal test duration. If there is not enough tests
for this period, increasing the number of days is
recommended. If it is not possible to acquire the
data for one month, the tank should be shutdown
and a normal test conducted.
Min CSLD history
14 days